| In
This Article:
A hole is cut into an
existing main heat duct and small 4 inch round duct is routed
to a point between the floor joists where a register can be
installed. A duct damper is installed to control the air flow. |
Related
Articles:
|
| Skill Level:
2-3 (Basic to Moderate) |
Time Taken:
About 4 Hours |
By
Bruce W. Maki,
Editor
In our old house remodeling project we made some minor changes to
the interior wall layout. The previous owner had turned an attic
into a master bedroom, but the only way to reach that bedroom was
through another bedroom. If you talk to real estate professionals,
they will tell you that such a weird layout will disqualify one of
those rooms from being considered truly a bedroom. That's a problem,
because it means the house can only be marketed as having 3 bedrooms
instead of 4.
So we framed a partition to form an entry hall to the master
bedroom. Of course, this meant robbing the other bedroom of a 3-foot
strip of floor area. There is enough room in this entry hall for
some shelving and maybe even a small built-in desk. I thought it
would be nice to have a little bit of heat too, since the small
space would be cut off from other sources of heat.
 |
This is the fireplace enclosure that will
allow us enough room to add another duct. |
|
| The lower part. |
 |
|
 |
The entry area to the master bedroom. A
little more heat here would be a good idea, because once
the walls are covered this small hallway will have no
heat source.
Since this area is at the center of the building it
may not need any heat, but the room it leads into lacks
sufficient heat, so I'm betting that installing a small
duct might help and won't hurt. I can always shut off
the air flow.
|
|
| The Big Deal: Drilling a 4˝"
hole.
We needed to make a big hole in the sub-floor so the
4" round duct could extend from the basement to
just below the second-story floor.
This is easy enough when you have a big drill (such
as this right-angle drill) and a hole saw. Otherwise,
this can be done with a jig saw or a reciprocating saw. |
 |
|
I bought a 4˝" hole saw because it can be used for many
projects, 4" metal ducting for dryer vents, 4" PVC pipe
for plumbing drains, etc.
 |
The hole viewed from the basement. The
rectangular duct on the right will be supplying the warm
air. |
|
| We temporarily connected several pieces of
ductwork to lay out the best location for the take-off.
We used a permanent marker to draw a line around the
outside of the take-off.
|
 |
|
 |
This is the take-off we used. There are
several other types of take-offs commonly available. |
|
| We drilled some 3/8" holes at the
corners of the 6˝" x 6˝" square cut-out. |
 |
|
 |
Using tin snips I cut out the opening in
the rectangular duct. |
|
| The take-off grabs onto the big duct using
these little metal tabs or fingers.
Here I'm demonstrating this on a piece of sheet
metal, not the actual duct. |
 |
|
 |
I put the take-off in the hole. This can
be challenging because ductwork components are not made
very precise. |
|
| I reached inside the take-off to fold over
the metal fingers. |
 |
|
 |
Next I installed a 5" to 4"
reducer fitting. |
|
| Then I installed an elbow. |
 |
|
 |
I dropped a 2 foot long piece of 4"
duct down through the hole and connected it to the
elbow. |
|
| The assembly so far.
But... before the duct leaves the basement it needs
to have a damper installed so the air flow can be
regulated.
|
 |
|
 |
I applied some metal foil duct tape to the
joints. For heating systems code requires tape that
carries the UL-181 rating.
Regular cloth duct tape is absolutely useless for
holding heating ducts together because within a year or
two the adhesive dries out.
|
|
Installing A Duct Damper:
| This is a 4" duct damper. There are
also dampers for 5" and 6" round ducts.
This is just a little flap that rotates and blocks
the flow of air.
|
 |
|
 |
I drilled two 5/16" holes, about 4
inches from the end of the straight duct segment.
The hardest part of this entire procedure is getting
two holes marked and drilled so they are exactly
opposite each other. If not, the damper may hit the side
of the duct and not close properly.
|
|
| On one end of the damper is a
spring-loaded threaded rod. The handle and wing-nut
fasten to this. |
 |
|
 |
I slipped the "dead" pin into
one of the holes, and compressed the "live"
spring-loaded pin as I pushed the damper into the duct. |
|
| With the damper in place the
"live" pin popped out through the other hole,
letting the damper rotate. |
 |
|
 |
When open, the damper looks kinda like
this. |
|
| I attached the handle and wing nut.
With most of these dampers, the handle positioned
perpendicular to the duct means that the duct is shut
off.
|
 |
|
 |
The corrected duct with damper.
The damper needs to be located where you can reach
it, such as in a basement, crawl space, or attic. There
is no point in putting dampers in a wall cavity where
they will be covered up. |
|
| The duct coming out of the floor needs to
jog to the side a couple of inches, so it will leave
room for a bookcase I plan to build on the sides of the
fireplace enclosure. |
 |
|
 |
I installed a pair of elbows, each set for
just a slight turn, to make the duct jog to the side.
Then I connected a 5 foot length of duct to the
elbows. |
|
| This shot is looking almost straight up.
I continued the duct upward, then added a couple of
elbows to jog around the fireplace chimney enclosure.
Note that at this point the duct is running just below
the level of the floor joists. |
 |
|
 |
Here is yet another jog to go above the
top plate and into the final joist bay. |
|
All these twists and turns cause extra resistance to air flow, so
it's best to avoid them. By making only a slight turn with some of
these elbows I can minimize the reduction in air flow.
The Final Cut:
| Since I couldn't find any sort of register
boot fitting or adapter for a 4" duct, I decided to
go the easiest route: I bought a 6" to 4x10 right
angle register boot fitting, and a 4" to 6"
reducer. |
 |
|
It's poor practice to increase the size of the duct,
because it makes the air velocity slow down, which might mean that
the air won't circulate well. Since this is a supplemental duct (I
could probably do without it) I'm not really concerned about perfect
warm air distribution.
 |
I laid out a location for the register.
I cut a 4" x 10" piece of plywood for a
template, just for kicks. |
|
| I drilled a hole in the floor, so I could
go downstairs and see where this point was located
relative to the floor joists. |
 |
|
 |
I cut out the 4" x 10" opening
with a jig saw. |
|
| To connect the 6" x 4x10 register
boot to the 6" to 4" adapter, I needed to make
a piece of duct with both ends crimped.
I used a duct crimping tool to make a series of
"bites" to the smooth end of the duct. |
 |
|
 |
Before I bought a crimping tool I had made
mediocre crimped ends with just a pair of needle-nose
pliers.
I would just grab a bit of metal and give it a twist,
then move over and do it again. It's not pretty, it
doesn't fit tightly, but it works in a pinch. |
|
If you are going to any significant amount of ductwork, it's
worth investing in a few tools, like the usual 3 types of tin snips
(straight, left turn, and right turn cutting) and the crimping tool.
| This is the creature I built.
It's kinda stupid, but it worked. If there is a
register boot available for 4" duct, it's not
carried at my local Home Depot.
I could have made my own register boot, but that
would take far more time than it's worth. |
 |
|
 |
I squeezed the "creature" into
the 4x10 register hole. It actually stayed there by
itself because the fit was so tight. |
|
| I cut the last piece of 4" duct and
connected it between the end of the duct and the
4-6" reducer. |
 |
|
 |
I drove in 4 sheet metal screws to hold
the register boot to the sub-floor.
I also need to add some supporting straps to keep the
duct from falling apart under its own weight. |
|
Supporting The Duct:
According to the book Code Check® HVAC (published by Taunton
Press and sold at Home Depot and others), metal ductwork needs
to be supported at least every 10 feet. There are many
methods available, such as telescoping metal brackets that are
simply hammered into the floor joists. I often just cut a scrap of
2x4 to fit between the floor joists and secure it with deck screws.
The duct at least needs something to support its weight,
but it may be acceptable if the duct can move slightly from
side-to-side.
I have seen lots of older ductwork that was supported by steel
wire that was strung between two nails driven into opposite floor
joists. I'm not sure if that is acceptable any more. Perforated
steel strap (plumber's tape) is often used to support ductwork.
Code Requirements:
There are many mechanical code requirements that affect duct
installations, such as:
Duct openings are not allowed in an attached garage. The
duct can pass through the garage, but you cannot run a new
household heating or cooling duct to serve the garage. I suppose
this could be very tempting for some handy-people who want to use
their attached garage as a workshop, but it's a code violation. A
garage needs its own separate heat source.
There must be fireblocking around a duct that passes
between floors. This can simply be a tight-fitting piece of wood. If
you hack a big oblong hole in the floor, the gaps around the duct
need to be filled. There is a special intumescent caulk (which
expands during a fire) for this purpose, and it's required in some
construction projects (like apartment complexes) but this stuff is expensive.
Regular Alex plus caulk probably does a decent job of fireblocking,
as would a piece of sheet metal.
|
Tools
Used:
- Cordless Drill/Driver
- Heavy-Duty Drill with 4˝"
Hole Saw
- Aviation-Style Tin Snips
- Duct Crimper
- Jig Saw
- Basic Hand Tools
|
Materials Used:
- 4" Galvanized Duct,
2' Long, 5' Long
- 4" Galvanized Elbows
- 4" Duct Damper
- 5" Take-off
- 5" to 4" Reducer
- Plumber's Tape, Sheet
Metal Screws
|
Back To Top
Of Page
Read our Disclaimer.
Search
Page
Home
What's New Project
Archives H.I.
World
Rants
Contact Us
|
|